Sunday, 8 Feb 2026
Subscribe
logo
  • Global
  • AI
  • Cloud Computing
  • Edge Computing
  • Security
  • Investment
  • Sustainability
  • More
    • Colocation
    • Quantum Computing
    • Regulation & Policy
    • Infrastructure
    • Power & Cooling
    • Design
    • Innovations
    • Blog
Font ResizerAa
Data Center NewsData Center News
Search
  • Global
  • AI
  • Cloud Computing
  • Edge Computing
  • Security
  • Investment
  • Sustainability
  • More
    • Colocation
    • Quantum Computing
    • Regulation & Policy
    • Infrastructure
    • Power & Cooling
    • Design
    • Innovations
    • Blog
Have an existing account? Sign In
Follow US
© 2022 Foxiz News Network. Ruby Design Company. All Rights Reserved.
Data Center News > Blog > Design > Harnessing Waste Heat is the Latest Frontier in Data Center Efficiency | DCN
Design

Harnessing Waste Heat is the Latest Frontier in Data Center Efficiency | DCN

Last updated: May 7, 2024 5:14 pm
Published May 7, 2024
Share
A thermal image of a data center
SHARE

Information facilities have been on an power effectivity drive for twenty years. They proceed to seek out methods to decrease power utilization, cool extra successfully, and cut back operational prices. The most recent frontier on this countless quest is the seize and reuse of waste warmth.

The amount of waste warmth is barely going to extend in information facilities as AI functions are added and extra liquid cooling is used. This rising pattern underscores the necessity for information facilities to undertake waste warmth reuse options, not solely to boost power effectivity but additionally to mitigate environmental influence and operational prices.High of Type

Associated: Information Facilities Now Want a Reactor’s Price of Energy, Dominion Says

“Warmth rejection from chips to the ability stays difficult,” mentioned Peter de Bock, Program Director for the ARPA-E COOLERCHIPS Program.

Whereas channeling waste warmth out of the ability is one method, it’s much more environment friendly and environmentally pleasant to make the most of waste warmth to generate energy, steam, heating, and even cooling. It is a vibrant space of analysis.

Associated: Specialists Discuss Liquid Cooling Methods to Handle AI Warmth Wave

“Services can cut back the fee burden and their carbon footprint by discovering methods to harness waste warmth,” mentioned Kyle Mangini who takes care of all laboratory and mechanical techniques on the Amherst College Science Center.

Multifunction Campuses

Brian Rener, Mission Essential Chief at SmithGroup, believes there are many sustainability and effectivity alternatives when information facilities are collocated inside multifunction buildings or campus settings. Since information facilities require steady cooling, they expel giant portions of waste warmth from servers and different gear that may be harnessed in varied methods to scale back total power consumption and additional decrease energy utilization effectiveness (PUE).

See also  Princeton Digital Plans 100MW Tokyo Hyperscale Data Center Campus

“As we anticipate a doubling of knowledge middle electrical energy consumption over the subsequent couple of years, most information facilities don’t have the choice of transferring to extra northerly places to make the most of cool outdoors air as a method to enhance sustainability,” mentioned Rener. “Alternatively, they will achieve worth from their waste warmth by collocating in mixed-used environments, inside campuses or turning into extra embedded inside native communities.”

Construct Good

Within the film ‘Subject of Goals,’ Ray Kinsella (Kevin Costner) is advised to, “Construct it and they’ll come.” He does so – in the course of an Iowa cornfield. That will have labored within the film, however Rener doesn’t see that as the very best place for a knowledge middle. Such a location makes it exhausting to maximise the worth of waste warmth. As an alternative, his recommendation is to hunt out a bigger group and have the info middle be a part of a broader power answer.

Rener backs up his assertion by citing some information from the US Vitality Data Administration (EIA) that exhibits area heating to be the biggest single power finish use in industrial buildings at 32%. Cooling was solely 9% however that quantity can be a lot bigger in Southern states. A single giant constructing consumes 1 MW for heating. 25 metropolis blocks require 10 MW, and an 8,500,000 sq. foot industrial property wants 100 MW for heating alone.

Now think about information middle density. Excessive-Efficiency Computing (HPC) and AI are driving rack densities to 100 kW and past. Aisles are being filled with processors with extra energy than ever.

“All processors are getting larger and warmer,” mentioned Shen Wang, principal analyst at Omdia. “Since 2000, the facility consumption of processors has elevated by 4.6 instances.”

This definitely poses a major problem when it comes to energy and cooling. Nevertheless it additionally opens up a chance as a result of sheer amount of a lot hotter waste warmth being emitted from chips and servers.

See also  KKR to Invest in Middle East’s Biggest Data Center Firm

Faculty Campus Cooling

Milwaukee Faculty of Engineering supplies a helpful case examine in waste warmth reuse. It added a pc science constructing with a supercomputer inside often known as Rosie. This Nvidia GPU-accelerated supercomputer helps college students examine AI, drones, robotics, and autonomous automobiles. Whereas the supercomputer room occupies just one,500sq.ft of the 65,000sq.ft construction, it consumes over 60% of its power. As such, the system wanted to be seamlessly built-in into the constructing and mechanical/electrical/plumbing infrastructure. The information middle is designed for N+1 redundancy, permitting it to stay purposeful even within the occasion of a single part failure, due to a number of backup turbines and cooling models.

The engineering staff developed a symbiotic relationship between the tutorial constructing power techniques and the supercomputer techniques. As an illustration, the pc room and educational constructing use the identical cooling system throughout summer time months, when the ability’s chilled water return line is used for information middle provide. By elevating the chilled water return, cooling efficiencies for the entire constructing have been elevated. Throughout the winter, when the tutorial constructing not requires mechanical cooling, the pc facility makes use of chilly outdoors air through devoted air-cooled roof-top condensers and built-in free-cooling circuits.

“The usage of waste warmth is essential in elevating information middle and constructing effectivity,” mentioned Jamison Caldwell, Principal Mechanical Engineer at SmithGroup.

In addition to discovering methods to harness waste warmth from sizzling aisles, he identified the liquid cooling gear additionally emits radiant warmth. He works on the power reuse issue which is calculated as a perform of reused power versus complete power consumed.  

See also  Milan's grid will allow tenfold data centre expansion

“There are quite a few campus-level alternatives for waste warmth,” mentioned Caldwell.  

NREL Vitality Restoration Loop

The Nationwide Renewable Vitality Lab (NREL) constructed an power techniques integration facility (ESIF) that was designed to match the heating calls for of its labs and places of work with its supercomputer-based information middle to make your complete constructing extra power environment friendly. It has achieved a PUE of 1.04, making it one of the crucial environment friendly information facilities on the planet.

“100% of workplace heating is finished by waste warmth reuse, and water use has been reduce in half,” mentioned Caldwell. “If there’s a sudden want for extra warmth, campus steam can be utilized.”

That is achieved courtesy of an power restoration water loop that spans campus heating and cooling techniques, supercomputing techniques, and legacy IT techniques, and gathers waste warmth from each liquid and air-cooling techniques. Caldwell characterised this as building-level power trade.

“Liquid cooling permits for larger grade hydronic warmth restoration,” he mentioned.

Incremental Positive factors

Liquid cooling might lead to a significant shift in information middle cooling effectivity and convey about drastically decrease PUEs – or no less than stop PUEs from rising as rack density soars. However Jason Matteson, vice chairman of buyer options structure at Iceotope, identified that the potential positive aspects from liquid cooling might be squandered because of varied areas of waste, together with an absence of sizzling air containment, lacking blanking panels, failure to switch power-hogging followers, and extra. 

“There may be quite a lot of waste current in most information facilities that we are able to eradicate,” mentioned Matteson.

Source link

Contents
Multifunction CampusesConstruct GoodFaculty Campus CoolingNREL Vitality Restoration LoopIncremental Positive factors
TAGGED: Center, data, DCN, efficiency, Frontier, Harnessing, Heat, Latest, Waste
Share This Article
Twitter Email Copy Link Print
Previous Article Cloud Computing News AI fuels almost 30% increase in IT modernisation spend, but firms are unprepared for data demands
Next Article responsible ai Research initiative launched to address questions about responsible AI use
Leave a comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Your Trusted Source for Accurate and Timely Updates!

Our commitment to accuracy, impartiality, and delivering breaking news as it happens has earned us the trust of a vast audience. Stay ahead with real-time updates on the latest events, trends.
FacebookLike
TwitterFollow
InstagramFollow
YoutubeSubscribe
LinkedInFollow
MediumFollow
- Advertisement -
Ad image

Popular Posts

Sony testing AI to drive PlayStation characters

As an organization and first-party platform, PlayStation and Sony haven't shied away from utilizing AI…

March 11, 2025

OpenAI warns California’s AI bill threatens US innovation

OpenAI has added its voice to the rising refrain of tech leaders and politicians opposing…

August 22, 2024

AMD holds steady against Intel in Q1

So, for the quarter, Intel’s share of the x86 market was 73.9%, a slight bump…

May 24, 2024

Memeagent Is Gaining Attention – Meeting Chad, the AI Agent That’s Changing the Game

Monrovia, Liberia, February twenty eighth, 2025, Chainwire Chad Leads the Manner: AI-Powered Memecoins Are Evolving…

February 28, 2025

Create the future with AI: Join Microsoft at NVIDIA GTC

Introduced by Microsoft and NVIDIA AI is producing tangible outcomes for enterprise at an astonishing…

February 17, 2025

You Might Also Like

Shutterstock Germany Only - News - Intel Factory Germany September 2024
Global Market

Intel sets sights on data center GPUs amid AI-driven infrastructure shifts

By saad
SpaceX
Global Market

Musk’s million data centers in space won’t fly, say experts

By saad
View on cooling towers of nuclear power plant thermal power station in which heat source is nuclear reactor, France, Europe, cheap energy source
Global Market

What hyperscalers’ hyper-spending on data centers tells us

By saad
atNorth expands Nordic footprint with new Stockholm data centre
Power & Cooling

atNorth expands Nordic footprint with new Stockholm data centre

By saad
Data Center News
Facebook Twitter Youtube Instagram Linkedin

About US

Data Center News: Stay informed on the pulse of data centers. Latest updates, tech trends, and industry insights—all in one place. Elevate your data infrastructure knowledge.

Top Categories
  • Global Market
  • Infrastructure
  • Innovations
  • Investments
Usefull Links
  • Home
  • Contact
  • Privacy Policy
  • Terms & Conditions

© 2024 – datacenternews.tech – All rights reserved

Welcome Back!

Sign in to your account

Lost your password?
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it.
You can revoke your consent any time using the Revoke consent button.